Page 443 - Bürkert
P. 443
50 x DN 5 x DN
Installation
EN ISO 5167-1 prescribes the straight inlet and outlet distances that must be complied with when installing fittings in pipe
40 x DN 5 x DN
lines in order to achieve calm flow conditions. The most important layouts that could lead to turbulence in the flow are shown
below, together with the associated prescribed minimum inlet and outlet distances. These ensure calm, problem-free meas-
urement conditions at the measurement point.
SE36 50 x DN 5 x DN 25 x DN 5 x DN
DN = orifice 40 x DN 5 x DN 20 x DN 5 x DN
Fluid direction -->
Regulating valve 2 x 90° elbow joint Extension
50 x DN 5 x DN 25 x DN 5 x DN 18 x DN 5 x DN
2 x 90° elbow joint 90° elbow joint
3 dimensional or T-piece Reduction
40 x DN 5 x DN 20 x DN 5 x DN 15 x DN 5 x DN
Dimensions [mm] 25 x DN 5 x DN 18 x DN 5 x DN
20 x DN 5 x DN 15 x DN 5 x DN
DN H with
S030 Fitting
06 160
08 160
H 15 165
18 x DN 5 x DN
20 163
25 163
32 166
40 170
15 x DN 5 x DN 177
50
65 177
442